Steam Trap Selection by Understanding Specifications
UNI KLINGER having various type of steam traps design irrespective to service & criticality
As like,
- Thermodynamic steam trap (UTD)
- Thermostatic steam trap (UTST)
- Bi-metallic steam traps
- Inverted bucket steam trap (UIBT)
- Ball Float steam trap (UFT)
How to select Traps & which parameters can be affect on steam trap performance &it’s efficiency:
Selection on Steam trap:
- Know your service/ application
- Location of trap i.e. reactor/ direct heating/ Indirect heating/ type of equipment coil (Jacketed/ Limpet coil)
- Total Qty of steam/ Condensate (Kg/hr)
- Operating pressure (Kg/cm2 g/ Bar g)
- Steam Inlet line size (NB/mm/ DN)
- Design Pressure drop of equipment (Reactor/ heat exchanger)
- Back pressure (Kg/cm2 g/ Bar g)
- Differential Pressure (Kg/cm2 g/ Bar g) which Inlet of traps & back pressure of downstream of trap (i.e. Delta P)
- Moreover, area where trap to be installed like atmospheric condition so that material of trap can be selected
- Sight Glass require wherever trap is in close system
Parameters which can affect on steam trap performance:
- Back pressure
- Under sizing of steam trap against high load
- Material of selection
- Customer don’t have exact detail of plant
- Wrong selection
- Wrong installation (Vertical/ Horizontal)
- Wrong differential selection of trap/ model
- End connection of trap against MOC of trap
For e.g.:
Service- Indirect steam heating limpet coil reactor
Steam Inlet Pressure- 3 bar g
Inlet size- 50 NB
Steam/ Condensate Flow- 380 Kg/hr
Pressure Drop of equipment- 0.5 bar g
Back pressure- 0.2 bar g
Selected Trap:
UKL Ball Float trap, Model- UFT 14 CI, DP- 4.5 Bar, Non IBR
End connection- SCR to BSP/ BSPT/ NPT
OrUFT 20 CS, DP-4.5 Bar, Non IBR End connection- F/E 150#
Size- 25 NB, 1 no. Qty
How Trap assembly looks:
CLOSED LOOP
OPEN LOOP
Selection on Trap selection:
Wherever for ease of maintenance, cleaning of trap always do prefer Flanged end connection trap so that trap can be remove within time & maintenance can be done immediately,
Now if in case very LP steam pressure application & prefers to install cast Iron then in such case choose screwed ends to BSP/ BSPT/ NPT,
In high pressure application above 10 Bar g & max do prefer Socket weld end so that chances of leakage will be very less because in sometime it may happens due to gasket wrong selection & gasket self life frequently leakage is occurs and then removal of trap time continues.
However in such case during welding procedure will require qualified IBR welders & whenever removal/ replacement of trap that time removal of cost & re-fitment cost is very high compare to screwed ends and Flanged end connections.
UKL trap carrying capacity chart for selection of Ball float trap:
Trap with Flanged end connection:
Trap with Screwed ends/ Socket weld ends: